TESTING LABORATORY
We put at your service a modern test laboratory amongst the best equipped in Northeast America.
We perform all tests on power transformers and equipment as per North-American and International standards such as IEEE, ANSI, CSA CEI or as per customer request.
- Shock generator, 160kV / 120kJ/ 8 stages for basic impulse level (BIL & SIL) and power surge of maneuver, voltage class Uu to 350kV
- Applied voltage test (Hi-Pot) 200kV / 200kVA
- CA source for load losses and temperature rise tests (90kW)
- Induced voltage tests (120Hz) up to 250kW with partial discharge measurements
POWER AND DISTRIBUTION TRANSFORMERS
ROUTINE TESTS (INDIVIDUAL TESTS)
- Winding insulation resistance measurement;
- Core insulation tests;
- Power factor insulation measurement;
- Single-phase excitation current measurement;
- Winding resistance measurement;
- Transformation ratio;
- Polarity and phase verification;
- No load losses and excitation current measurement;
- Load losses and impedance calculation;
- Lightning impulse (BIL) and switching surge (SIL)
- Homopolar impedance measurement;
- Power surge maneuver tests (345kV and higher);
- Applied voltage at industrial frequency
(Hi-Pot); - Induced voltage with partial discharge measurement tests;
- On load and off-load tap changer operations;
- Applied voltage on auxiliary circuits tests;
- Dissolved gas analysis;
- Tank and radiator sealing verification.
TYPE TESTS
- Power surge maneuver tests;
- Temperature rise and temperature rise overload tests;
- Audible noise measurement.
SPECIAL TESTS
- External radio disturbances measurement
DIAGNOSTIC
DETECTION AND LOCATION IN CASE OF FAULT DURING TESTS – EXTERNAL SERVICES
FAULT DURING INDUCED VOLTAGE TESTS:
DIAGNOSE AND LOCATE THE FAULT DURING TESTS WITH PARTIAL DISCHARGE MEASUREMENTS
- Pattern Recognition in Partial Discharges (PRPD);
- Locate fault with sensors;
- If required, complement by multi-term electrical method;
- A work report will be provided, confirming location of transformer internal fault if a signal is detected.
FAULT DURING BIL OR MANEUVER:
DIAGNOSE AND LOCATE THE FAULT
- In case of a fault during BIL, a fault detection can be done;
- Using of sensors;
- A work report will be provided, confirming location of the transformer internal fault if a signal is detected.